<p>Air cooled compressed air aftercoolers cools the compressed air with atmospheric air. The compressed air is cooled to approximately 9oC above ambient temperature. A sufficient capacity aftercooler can take upto 80% of the moisture present in the compressed air. The TB Series is a complete aftercooler package designed to work on most models of rotary air compressors. To select the appropriate model, simply determine compressor horse power, and select model from the chart.</p><p>Sizing Notes, Recommendations are based on the following:-<b>Heat Removal : </b>After cooler = Compressor horsepower x 1.15 ( motor service factor ) x .17 (this assumes 17% of input horsepower is rejected to heat).<b>15oF Approach Temperature : </b>Compressor air outlet temperature – ambient air temperature.<b>Temperatures : </b>Ambient Air Temperature + 15oF = Compressed Air Outlet Temperature.<b>Flows : </b>Compressor Horsepower x 4.5 = SCFM Air Flow.</p><p>Air flow rates are based on less than a 4 PSI pressure drop @ 100 PSI operating & 100oF ambient and 50% relative humidity.</p>